DFS-1
DFS-1
INSTALLATION AND
OPERATION
INSTRUCTION MANUAL
PRODUCTION RELEASE
AUGUST, 1994
MICROPROCESSOR BASED
BRUSHLESS D.C.
MOTOR CONTROLLER
SOFTWARE RELEASE 1.0
SOFTWARE RELEASE 1.0
POWERTEC
Industrial Motors
Vista de página 0
1 2 3 4 5 6 ... 83 84

Resumo do Conteúdo

Página 1 - Industrial Motors

DFS-1DFS-1INSTALLATION ANDOPERATIONINSTRUCTION MANUALPRODUCTION RELEASEAUGUST, 1994MICROPROCESSOR BASEDBRUSHLESS D.C.MOTOR CONTROLLERSOFTWARE RELEASE

Página 2 - Shipping Addre

Page 5Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©Programmable analog inputs and analog outputsallow many possibilities for control through externalv

Página 3 - DFS-01IM

Page 6DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©SUMMARY OF WARRANTY AND DISCLAIMERPOWERTEC Industrial Corporation warrants the DFS-1 to be free fro

Página 4 - Additional Info

Page 7Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©T1T2T312345678910Motor+24VDigital Out 1ADigital Out 1BDigital Out 2ADigital Out 2BDigital Out 3ADig

Página 5 - 1.0 INSTALLATION

Page 8DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©MOTOR ENCODER CABLE:The motor encoder cable is connected to plug-interminal strip TB1:A on the DFS-

Página 6 - CONTENTS

Page 9Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©The default speed reference input is AnalogInput #1, located on TB1:B. The default input is fora 0

Página 7

Page 10DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©FREQUENCY OUTPUT:There are two outputs available to supply afrequency for external use.The first i

Página 8

Page 11Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©The programmable inputs (TB2-A4 throughTB2-A10) may be programmed for jog, thread, orother preset

Página 9

Page 12DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 10 - INTRODUCTION

Page 13Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©DEFAULT SETUPThe concept behind the DFS-1 calls for fullyprogrammable inputs and outputs. The abil

Página 11 - WARNING!

Page 14DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 12 - 1.0 CONNECTIONS

A subsidiary ofPOWERTEC Industrial CorporationMailing Address: P.O.Box 2650 • Rock Hill, South Carolina USA 29732 • PHONE: 803-328-1888Shipping Addres

Página 13 - ANALOG INPUTS:

Page 15Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©5.0 Each of the two inputs may be set up one ofsix ways:1. -10 to +10 VDC2. 0 to +10 VDC3. 0 to 5

Página 14 - FREQUENCY INPUT:

Page 16DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©FREQUENCY INPUTS ANDOUTPUTSThere is one frequency input and there are twofrequency outputs availab

Página 15 - DIGITAL INPUTS:

Page 17Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©COMMUNICATIONSStandard: RS-485Data Rates: 300, 600, 1200, 2400, 4800, 9600,19.2K, and 38.4K baudA

Página 16 - POWERTEC Ind. Corp.©

Page 18DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 17 - DFS-1 Manual Revised 7/95

Page 19Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©DFS-1 parameters are stored as DOUBLEWORD values (32 bits), regardless of the actual sizeof the da

Página 18 - DEFAULT SETUP

Page 20DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©0001b) , the Run FUNCTION cannot be controlledfrom the terminal strip, but can only be controlled

Página 19

Page 21Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©0000h Normal current limits (motor currentnot limited at a lower level)0001h Motoring torque setpo

Página 20 - 2.0 SPECIFICATIONS

Page 22DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©8. MASTER RAMP UP TIMEUSE PARAMETER #8 TO SET THE TIME TORAMP FROM ZERO TO FULL SPEED.RANGE OF VAL

Página 21 - DIGITAL OUTPUTS

Page 23Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©tionship between motor speed and EGU is defined inparameter #14, which sets the value of EGU’s at

Página 22 - COMMUNICATIONS

Page 24DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©are implied. Therefore, the maximum ratio setpointis 9.999.17. ANALOG INPUT #1 MODESELECTUSE PARA

Página 23

[ST2] - 7 6 5 4 3 2 1 0Local/Remote (0,1)Master/slave (0,1)At Speed (1)Fwd. Dir. SetFault Detected (1)Drive Enabled (1)Microprocessor FaultZero Speed[

Página 24 - 3.0 DFS-1 PARAMETERS

Page 25Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©As a Speed Reference input ( ...01h), Analoginput #1 sets the speed of the controlled motordirectl

Página 25 - 5. MODES OF OPERATION

Page 26DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©20. ANALOG INPUT #1 HIGHENGINEERING UNITS (EGU)USE PARAMETER #18 TO SELECT THE MAXI-MUM ANALOG INP

Página 26 - REVOLUTION

Page 27Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©25. ANALOG OUTPUT #1 MODESELECTUSE PARAMETER #25 TO SELECT THESOURCE OF A SIGNAL AT ANALOGOUTPUT #

Página 27 - 11. SLAVE RAMP DOWN TIME

Page 28DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©29. ANALOG OUTPUT #2 LOWENGINEERING UNITS (EGU)USE PARAMETER #29 TO SELECT THETHRESHOLD OF ANALOG

Página 28 - 14. ENGINEERING UNITS

Page 29Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©31. DIGITAL INPUT #1 FUNCTIONUSE PARAMETER #31 TO SELECT THE #1DIGITAL INPUT FUNCTION.RANGE OF VAL

Página 29 - 16. MAXIMUM RATIO

Page 30DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©35. DIGITAL INPUT #5FUNCTIONUSE PARAMETER #35 TO SELECT THE #5DIGITAL INPUT FUNCTION.RANGE OF VALU

Página 30 - ENGINEERING UNITS (EGU)

Page 31Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©39. DIGITAL OUTPUT #2FUNCTIONUSE PARAMETER #39 TO SELECT THE #2DIGITAL OUTPUT FUNCTION.RANGE OF VA

Página 31

Page 32DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©limit the output DRIVE current to 150%. Thisparameter CANNOT OVERRIDE that limit, but thisparamet

Página 32

Page 33Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©When parameter #48 is set to 0000 0000h, theDFS-1 is in the JUMP mode. In MASTER mode (setby param

Página 33 - 30. ANALOG OUTPUT #2 HIGH

Page 34DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©53. INPUT DEBOUNCE VALUEUSE PARAMETER #53 TO SET THE LENGTH OFTIME AN INPUT MUST BE ACTIVE TO BEAC

Página 34

Additional InfoDFS Software Modification ForDynamic Braking or Output ContactorOperation25 October, 1994Functional DescriptionA new function for Conta

Página 35

Page 35Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©58. SLAVE JOG RATIOUSE PARAMETER #58 TO SET A JOG SPEEDWHICH CAN BE TOGGLED IN AND OUT.RANGE OF VA

Página 36

Page 36DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 37

Page 37Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©4.0 DFS - 1 SETUP Making parameter changes requires the optionalkeypad display unit or a compute

Página 38

Page 38DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©6. SET PARAMETER #42 FOR THE DRIVEGAIN.This value is defaulted to 50% of the range andtherefore se

Página 39

Page 39Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©1. SET PARAMETER #5 FOR THE MASTERMODE.Set the basic operation in this parameter toMASTER.This par

Página 40 - 62. CONTACTOR DELAY

Page 40DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©1. SET PARAMETER #5 FOR THE SLAVEMODE.Set basic operation in this parameter to 1 for SLAVEmode. Fo

Página 41

Page 41Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©4.4 INPUTS AND OUTPUTS SETUP1. SET PARAMETERS #17, #18, #19, AND #20TO SET UP ANALOG INPUT #1.If

Página 42 - 4.0 DFS - 1 SETUP

Page 42DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©3. SET PARAMETER #3 TO SELECT WHICHFUNCTIONS ARE REMOTE.This parameter may be used to include or e

Página 43

Page 43Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©ERROR CODES FOR ON-BOARD DISPLAYThe DFS-1 has a single-digit alphanumeric display to show error co

Página 44 - 4.2 MASTER MODE SETUP

Page 44DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 45 - 4.3 SLAVE MODE SETUP

Page 1Figure 2: The Model 1000 chassisFigure 1: The DFS-1 replaces two boards.If the board is being installed to replace theboards on a standard co

Página 46 - 4.4 INPUTS AND OUTPUTS SETUP

Page 45Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©6.0 COMMUNICATIONS PROTOCOLGENERAL DEFINITIONS:[STX] - 02h - Start of data[ETX] - 03h - End of da

Página 47 - 4.5 COMMUNICATIONS SETUP

Page 46DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©COMMAND LISTFollowing is a list of commands to the unit.Detailed descriptions of each command are

Página 48 - 5.0 DFS - 1 ERROR CODES

Page 47Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©PARAMETER LIST:Following is a list of the parameters used inDFS-1. For a detailed description of

Página 49

Page 48DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©ATTACHMENT A: DETAILED COMMANDS Read Speed/Status (81)Command: Read Speed/StatusDescription:This

Página 50 - 6.0 COMMUNICATIONS PROTOCOL

Page 49Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©Message:[DLE][STX][UID][CMD][DLE][ETX][CSM]Response:If no errors and unit i.d. does not equal 0[DL

Página 51 - COMMAND LIST

Page 50DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©[ERR] - Reported error[80] - Unit not in remote mode[84] - Illegal channel number[86] - Illegal Co

Página 52 - PARAMETER LIST:

Page 51Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©Response:If no errors[DLE][STX][UID][ACK][VL4][VL3][VL2][VL1][DLE][ETX][CSM]else[DLE][STX][UID][NA

Página 53

Page 52DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©Definitions:[DIG] - Digital output number 01 to 04[VL4] - Always 00[VL3] - Always 00[VL2] - Alw

Página 54

Page 53Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©Message:[DLE][STX][UID][CMD][00][00][SMH][SML][DLE][ETX][CSM]Response:If no errors[DLE][STX][UID][

Página 55

Page 54DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©Application Mode (8F)Command: Application Mode CommandDescription:This command reads/sets the ope

Página 56

CONTENTSIntroduction ...1S

Página 57

Page 55Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©Additional InfoDFS SOFTWARE MODIFICATION FORDYNAMIC BRAKING OR OUTPUT CONTACTOROPERATIONFunctional

Página 58

Page 56DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©+24VDigital Out 1ADigital Out 1BDigital Out 2ADigital Out 2BDigital Out 3ADigital Out 3BDigital Ou

Página 59 - PARAMETER DESCRIPTION:

Page 57Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©+24VDigital Out 1ADigital Out 1BDigital Out 2ADigital Out 2BDigital Out 3ADigital Out 3BDigital Ou

Página 60

Page 58DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 61 - Connections

Page 59Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©APPENDIX ARETROFITTING THE MODEL 1000, 1000A, OR 1000ARThe DFS-1 Model 1000 series retro-fit kit c

Página 62 - Dynamic Braking

Page 60DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 63

Page 61Revised 7/95 DFS-1 ManualPOWERTEC Ind. Corp.©APPENDIX BMENU AND KEYPAD HIERARCHYWhen the DFS-1 is shipped, the factory presetsthe unit’s parame

Página 64 - APPENDIX A

Page 63DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGURE 1Fig. 2Fig. 30*ParametersEnterHistoryEnterStatusMenuEnb/Dsb BkltEnterContrastEnterTimeEnter

Página 65

Page 64DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 66 - APPENDIX B

Page 65DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CAnalog InEnterFIGURES 2 - 4Fig. 2Fig. 2Fig. 4SelectAnalog OutEnterDigital InEnterDigital OutEnterU

Página 67 - * Not visible in some modes

23. ANALOG INPUT #2 LOW ENGINEERING UNITS (EGU)... 2224. ANALOG INPUT #2 HIGH ENGINEERING U

Página 68 - POWERTEC Ind. Corp

Page 66DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 69 - DFS-1 Manual

Page 67DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CMinimum RatioEnterPreset Ratio 1EnterFIGURES 5 - Fig. 5SlaveEnterEnterFig. 2SelectSelectPreset 2En

Página 70

Page 68DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 71

Page 69DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFig. 13Fig. 13Fig. 4Analog InEnterChannel # 1EnterSelectSelect.Fig. 9Channel # 2EnterFig. 10Fig. 4

Página 72

Page 70DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 73

Page 71DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGUREFig. 14Fig. 9Low EGUEnterEnterAI Channel#1or2ModeEnterSelectSelect.High EGUEnterFig. 13Fig.

Página 74

Page 72DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 75

Page 73DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGUREFig. 17 Fig. 18Fig. 16Fig. 20Fig. 19Fig. 11Fig. 19Fig. 18FigDI ModeEnterGeneral PurposeEnter

Página 76

Page 74DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 77 - Fig. 17 Fig. 18

Page 75DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGUREFig. 23Fig. 22Fig. 12 Fig. 21Fig. 21 Fig. 22 Fig. 23Fig. 21 Fig. 7DO Channel#1or2EnterModeEn

Página 78

5.0 DFS-1 ERROR CODES ...396.0 COMMUNICATION PROTOCOL

Página 79 - Fig. 21 Fig. 22 Fig. 23

Page 76DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 80

Page 77DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGURESFig. 7Regen I LimitEnterHorsepowerEnterFig. 25 Fig. 26Pulse MultiplierEnterX1EnterSelectSel

Página 81

Page 78DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 82

Page 79DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CFIGURES 29 - 30Fig. 29Fig. 7Fig. 30Fig. 1Setpoint ControlEnterFreezeEnterSelectSelectFloatEnterHis

Página 83

Page 80DFS-1 ManualRevised 7/95POWERTEC Ind. Corp. CTHIS PAGE WAS INTENTIONALLY LEFT BLANK.

Página 84

Page 4DFS-1 Manual Revised 7/95POWERTEC Ind. Corp.©THIS PAGE WAS INTENTIONALLY LEFT BLANK.